Overview
A Direct Expansion Air Handling Unit integrates a DX coil directly within the unit. Instead of using chilled water to cool the air, the DX coil uses refrigerant that absorbs heat from the air passing over it. This design eliminates the need for a separate chilled water system, making DX AHUs compact, simpler to install, and ideal for small to medium-sized applications.
|
performance |
Air volume |
Residual Pressure |
Cooling volume ( K W ) |
Heat volume ( K W ) |
Water volume(T/h) |
Water reistance(KPa) |
power |
Noice |
Weight |
||||
|
Return Air |
Fresh Air |
Return Air |
Fresh Air |
Return Air |
Fresh Air |
Return Air |
Fresh Air |
||||||
|
BFP-20W/L |
2000 |
200 |
11.2 |
22.5 |
19.1 |
28.00 |
1.9 |
3.9 |
3.5 |
4.2 |
0.32 |
55 |
140/160 |
|
BFP-20XW/L |
160 |
13.9 |
29.7 |
25.7 |
32.67 |
2.4 |
5.1 |
4.5 |
5.6 |
160/190 |
|||
|
BFP-30W/L |
3000 |
260 |
16.8 |
33.8 |
28.6 |
42.00 |
2.9 |
5.8 |
4.5 |
6.4 |
0.55 |
56 |
160/180 |
|
BFP-30XW/L |
220 |
20.8 |
44.5 |
38.5 |
49.00 |
3.6 |
7.7 |
5.3 |
8.5 |
180/210 |
|||
|
BFP-40W/L |
4000 |
340 |
22.4 |
45.1 |
38.1 |
56.00 |
3.9 |
7.7 |
4.6 |
6.7 |
0.75 |
58 |
195/220 |
|
BFP-40XW/L |
300 |
27.7 |
59.3 |
51.3 |
64.33 |
4.8 |
10.2 |
6.5 |
12.4 |
225/255 |
|||
|
BFP-45W/L |
4500 |
320 |
25.2 |
50.7 |
42.9 |
63.00 |
4.3 |
8.7 |
5.2 |
8.6 |
0.75 |
58 |
205/220 |
|
BED-45XW/ |
280 |
31.2 |
66.8 |
57.8 |
73.50 |
5.4 |
11.5 |
7.4 |
15.4 |
215/235 |
|||
|
BFP-50W/L |
5000 |
500 |
28.0 |
56.3 |
47.7 |
70.00 |
4.8 |
9.7 |
6.8 |
10.7 |
1.1 |
59 |
220/235 |
|
BFP-50XW/L |
460 |
34.7 |
74.2 |
64.2 |
81.67 |
6.0 |
12.8 |
8.1 |
19.5 |
230/255 |
|||
|
BFP-55W/L |
5500 |
500 |
30.8 |
62.0 |
52.4 |
77.00 |
5.3 |
10.7 |
6.5 |
12.7 |
1.5 |
59 |
238/256 |
|
BFP-55XW/L |
460 |
38.1 |
81.6 |
70.6 |
89.83 |
6.6 |
14.0 |
9.5 |
20.3 |
256/286 |
|||
|
BFP-60W/L |
6000 |
500 |
33.6 |
67.6 |
57.2 |
84.00 |
5.8 |
11.6 |
7.4 |
14.8 |
1.5 |
60 |
258/285 |
|
BFP-60XW/L |
460 |
41.6 |
89.0 |
77.0 |
98.00 |
7.2 |
15.3 |
11.3 |
28.2 |
285/306 |
|||
|
BFP-70W/L |
7000 |
500 |
39.2 |
78.9 |
66.7 |
98.00 |
6.7 |
13.6 |
8.5 |
16.5 |
1.8 |
61 |
282/312 |
|
BFP-70XW/L |
460 |
48.5 |
103.8 |
89.8 |
114.33 |
8.3 |
17.9 |
14.6 |
33.3 |
315/346 |
|||
|
BFP-80W/L |
8000 |
600 |
44.8 |
90.1 |
76.3 |
112.00 |
7.7 |
15.5 |
9.06 |
18.4 |
2.2 |
62 |
310/345 |
|
BFP-80XW/L |
560 |
55.5 |
118.7 |
102.7 |
130.67 |
9.5 |
20.4 |
16.4 |
39.6 |
338/369 |
|||
|
BFP-90W/L |
9000 |
600 |
50.4 |
101.4 |
85.8 |
126.00 |
8.7 |
17.4 |
10.6 |
22.4 |
2.2 |
63 |
322/358 |
|
BFP-90XW/L |
560 |
62.4 |
133.5 |
115.5 |
147.00 |
10.7 |
23.0 |
18.2 |
43.6 |
345/369 |
|||
|
BFP-100W/L |
10000 |
600 |
56.0 |
112.7 |
95.3 |
140.00 |
9.6 |
19.4 |
12.4 |
26.7 |
3.0 |
64 |
336/368 |
|
BFP-100XW/L |
560 |
69.3 |
148.3 |
128.3 |
163.33 |
11.9 |
25.5 |
21.6 |
48.6 |
356/389 |
|||
|
BFP-120W/L |
12000 |
600 |
67.2 |
135.2 |
114.4 |
168.00 |
11.6 |
23.2 |
18.7 |
40.1 |
1.8×2 |
64 |
438/475 |
|
BFP-120XW/L |
560 |
83.2 |
178.0 |
154.0 |
196.00 |
14.3 |
30.6 |
28.4 |
53.2 |
476/506 |
|||
|
BFP-150W/L |
15000 |
600 |
84.0 |
169.0 |
143.0 |
210.00 |
14.4 |
29.1 |
22.6 |
42.6 |
2.2×2 |
64 |
520/550 |
|
BFP-150XW/L |
560 |
104.0 |
222.5 |
192.5 |
245.00 |
17.9 |
38.3 |
35.7 |
73.5 |
562/598 |
|||
|
BFP-180W/L |
18000 |
600 |
1008 |
202.8 |
171.6 |
252.00 |
17.3 |
34.9 |
25.1 |
44.2 |
3.0×2 |
65 |
556/581 |
|
BFP-180XW/L |
560 |
124.8 |
267.0 |
231.0 |
294.00 |
21.5 |
45.9 |
47.6 |
78.2 |
585/615 |
|||
|
BFP-200W/L |
20000 |
600 |
112.0 |
225.3 |
190.7 |
280.00 |
19.3 |
38.7 |
28.7 |
46.5 |
3.0×2 |
65 |
576/595 |
|
BFP-200XW/L |
560 |
138.7 |
296.7 |
256.7 |
326.67 |
23.8 |
51.0 |
51.6 |
82.6 |
610/638 |
|||
|
BFP-230W/L |
23000 |
650 |
1288 |
259.1 |
219.3 |
322.00 |
22.1 |
44.6 |
29.7 |
48.7 |
4.0×2 |
68 |
612/635 |
|
BFP-230XW/L |
600 |
159.5 |
341.2 |
295.2 |
375.67 |
27.4 |
58.7 |
51.6 |
85.2 |
639/672 |
|||
|
BFP-250W/L |
25000 |
650 |
140.0 |
281.7 |
238.3 |
350.00 |
24.1 |
48.4 |
26.5 |
49.6 |
4.0×2 |
69 |
652/685 |
|
BFP-250XW/L |
600 |
173.3 |
370.8 |
320.8 |
408.33 |
29.8 |
63.8 |
50.2 |
82.6 |
710/732 |
|||
|
BFP-280W/L |
28000 |
650 |
156.8 |
315.5 |
266.9 |
39200 |
27.0 |
54.2 |
32.6 |
43.6 |
5.5×2 |
70 |
679/712 |
|
BFP-280XW/L |
600 |
194.1 |
415.3 |
359.3 |
457.33 |
33.4 |
71.4 |
54.5 |
92.5 |
729/758 |
|||
|
BFP-300W/L |
30000 |
650 |
168.0 |
338.0 |
286.0 |
420.00 |
28.9 |
58.1 |
36.9 |
52.3 |
5.5×2 |
70 |
712/735 |
|
BFP-300XW/L |
600 |
208.0 |
445.0 |
385.0 |
490.00 |
35.8 |
76.5 |
57.2 |
91.2 |
765/796 |
|||
|
BFP-350W/L |
35000 |
650 |
196.0 |
394.3 |
333.7 |
490.00 |
33.7 |
67.8 |
38.7 |
59.4 |
7.5×2 |
72 |
826/998 |
|
BFP-350XW/L |
600 |
242.7 |
519.2 |
449.2 |
571.67 |
41.7 |
89.3 |
58.7 |
96.2 |
910/1110 |
|||
Return Air Conditions:
- Cooling: Inlet air dry-bulb temperature is 27°C, wet-bulb temperature is 19.5°C; inlet water temperature is 7°C with a water temperature difference of 5°C between inlet and outlet.
- Heating: Inlet air dry-bulb temperature is 15°C; hot water inlet temperature is 60°C.
Fresh Air Conditions:
- Cooling: Inlet air dry-bulb temperature is 34°C, wet-bulb temperature is 28°C; inlet water temperature is 7°C with a water temperature difference of 5°C between inlet and outlet.
- Heating: Inlet air dry-bulb temperature is -4°C; hot water inlet temperature is 60°C.
Key Features
●DX Coil Integration:
The DX coil contains refrigerant that evaporates directly within the coil to cool the air. In heating mode, the cycle can be reversed to deliver warmth.
●Compact Design:
Without the need for additional water-loop components (like chillers, pumps, and extensive piping), the overall footprint of the unit is reduced-beneficial for space-constrained installations.
●Simplified Installation:
Fewer components translate to a streamlined installation process and easier maintenance since there's no water treatment or plumbing system involved.
●Zoned Control:
Many DX AHUs offer the ability to control different zones independently, allowing tailored temperature management for various areas within a building.
●Energy Efficiency:
For smaller loads, the direct expansion method can be more energy efficient by reducing energy losses inherent in water-based heat transfer systems.
Applications
●Commercial Buildings:
Ideal for small to medium-sized office spaces, retail outlets, and restaurants where a large-scale chilled water system isn't justified.
●Residential Complexes:
Suitable for apartment buildings and condos that need efficient, localized air conditioning without the infrastructure for a chilled water system.
●Mixed-Use Developments:
DX AHUs can serve different zones with varying cooling or heating loads, making them flexible for buildings with diverse occupancy patterns.




FAQ
Q: Can products be produced according to customer requirements?
Q: Is it allowed to visit the factory?
Q: Are you looking for agents?
Q: How do you resolve issues if there are malfunctions during the use of the equipment?
Q: What software do you use for your product drawings?
Hot Tags: direct expansion air handling unit, China direct expansion air handling unit manufacturers, suppliers, factory, fan coil unit, Desiccant Dehumidification Unit, Residential Heat Recovery Ventilator, Four Pipe Fan Coil Unit, energy recovery ventilator, Cooling and Heating Fan Coil Unit